KAC-ABC-R/Q
AI

The **KAC-ABC-R/Q** refers to a series of electronic modules specifically used in **Addressable Fire Alarm Systems**, typically manufactured by KAC Alarm Company (a subsidiary of Honeywell). These are commonly used as interface modules to bridge conventional devices or auxiliary equipment into an addressable loop.
---
## 1. Core Technical Specifications
The "R/Q" suffix usually denotes specific mounting or functional variants (such as Relay output or Monitored Input).
| Feature | Specification Details |
| :--- | :--- |
| **Communication Protocol** | Proprietary Addressable Loop (e.g., Morley-IAS, System Sensor) |
| **Operating Voltage** | 15V - 32V DC (Loop powered) |
| **Standby Current** | ~300μA - 500μA |
| **Addressing Method** | Rotary Switches (01-99 or 01-159) |
| **Terminal Connections** | Screw terminals (0.5mm² to 2.5mm²) |
| **Operating Temperature** | -20°C to +60°C |
---
## 2. Key Electronic Components
The internal PCB of these modules consists of several critical stages to ensure safety and reliability:
### A. The Microprocessor & ASIC
The heart of the module is an Application Specific Integrated Circuit (ASIC) or a low-power microcontroller. This chip handles:
* **Decoding:** Interpreting the polling data from the Fire Alarm Control Panel (FACP).
* **Addressing:** Reading the physical position of the rotary switches.
### B. Loop Isolation (Optional)
Many "R/Q" variants include a built-in **Short Circuit Isolator**.
* **Function:** If a short circuit occurs on the loop, the electronic switch opens to prevent the entire loop from failing.
* **Component:** High-speed MOSFETs triggered by overcurrent sensing circuitry.
### C. Input/Output Interfacing
* **Relay (R variant):** Contains a latching or non-latching electromechanical relay. This allows the system to trigger external hardware like door magnetic holders or fire shutters.
* **Monitoring Circuit (Q/Input variant):** Uses an End-of-Line (EOL) resistor to monitor for "Open Circuit" or "Short Circuit" conditions on the external wiring.
---
## 3. Physical Layout and Wiring
The module is typically housed in a plastic enclosure designed for DIN-rail mounting or surface boxes.
```markdown
Terminal Block Layout (Typical):
1. Loop In (+)
2. Loop In (-)
3. Loop Out (+)
4. Loop Out (-)
5. Relay Contact / Input (+)
6. Relay Contact / Input (-)
```
---
## 4. Addressing Logic
The module uses two **Rotary Decadic Switches** to set the address.
* **TENS Switch:** Sets the first digit (0-15).
* **UNITS Switch:** Sets the second digit (0-9).
* *Example:* Setting TENS to '4' and UNITS to '2' assigns the device Address 42.
---
- ⤷
What is the specific difference between the 'R' and 'Q' model variants?
- ⤷ How do you calculate the EOL resistor value for the input monitoring circuit?
- ⤷ Are these modules compatible with generic 24V conventional panels?