29 / 42 page ![]() Type büS büS network shielding 29 11.5 Network with none shield connected devices Not recommended to have “None” shield connected devices only. Network shield would be floating at all and this is equal to unshielded. When using devices without an internally connected shield, take care that one end of büS shield must be connected directly to FE. Either a direct or RC shield connection can be used at the other shield end. The devices of the shielding type "None" are located in between with minimal stitches (e.g. with T-piece). ▪ For this, use either devices at the ends of network. Device 3 (None) Device 4 (RC) Device 2 (None) Device 1 (Direct) Fig. 31: büS network with devices without internal shield connection (shielding "None") ▪ Or connect cable shield directly to FE on both ends (example). Device 3 (None) Device 4 (None) Device 2 (None) Device 1 (None) Equipotential, clean FE area Fig. 32: büS network with devices without internal shield connection (shielding "None") |
|
링크 URL |
| ALLDATASHEET 가 귀하에 도움이 되셨나요? [ DONATE ] |
Alldatasheet는? | 광고문의 | 운영자에게 연락하기 | 개인정보취급방침 | 링크 투 데이터시트 | 링크교환 | 제조사별 검색 All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|