  E3S-LS3RC4 Datasheet HTML 1Page - Omron Electronics LLC E3S-LS3RC4 Datasheet HTML 2Page - Omron Electronics LLC E3S-LS3RC4 Datasheet HTML 3Page - Omron Electronics LLC E3S-LS3RC4 Datasheet HTML 4Page - Omron Electronics LLC E3S-LS3RC4 Datasheet HTML 5Page - Omron Electronics LLC E3S-LS3RC4 Datasheet HTML 6Page - Omron Electronics LLC E3S-LS3RC4 Datasheet HTML 7Page - Omron Electronics LLC E3S-LS3RC4 Datasheet HTML 8Page - Omron Electronics LLC  
Zoom Inzoom in Zoom Outzoom out
 7 / 8 page
background image
E3S-LS
E3S-LS
7
Precautions
Sensing Distance Adjustment
E3S-LS10XE4
Adjustment Method
1. Set the pointer of the sensitivity adjuster to the center of its
revolution range.
2. Turn the distance adjuster fully counterclockwise to the “S”
position.
3. Set the sensing object in position.
4. Turn the distance adjuster gradually clockwise to a point
where both the LIGHT and STABILITY indicators light. Fix the
distance adjuster at that point.
5. Adjust sensitivity.
Distance adjuster
Object sensed
Background object
E3S-LS20XE4
Adjustment Method 1
When the quantity of light reflected from the object is greater than
that from the background object, adjust the sensing distance in the
following sequence:
1. Set the pointer of the sensitivity adjuster to the center of its
revolution range.
2. Turn the distance adjuster fully counterclockwise to the “S”
position.
3. Set the sensing object in position.
4. Turn the distance adjuster gradually clockwise to a point
where both the LIGHT and STABILITY indicators light. Fix the
distance adjuster at that point.
5. Adjust sensitivity.
Distance adjuster
Object sensed
Background object
Adjustment Method 2
When the quantity of light reflected from the object is greater than
that from the background object, adjust the sensing distance in the
following sequence:
1. Set the pointer of the sensitivity adjuster to the center of its
revolution range.
2. Turn the distance adjuster fully counterclockwise to the “L”
position.
3. Remove the sending object.
4. Turn the distance adjuster gradually clockwise to a point
where both the LIGHT and STABILITY indicators light. Fix the
distance adjuster at that point.
5. Adjust sensitivity.



Html Pages

1 2 3 4 5 6 7 8


데이터시트 다운로드

Go To PDF Page


링크 URL



ALLDATASHEET 가 귀하에 도움이 되셨나요?  [ DONATE ] 

Alldatasheet는?   |   광고문의   |   운영자에게 연락하기   |   개인정보취급방침   |   링크 투 데이터시트    |   링크교환   |   제조사별 검색
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com