RM4850 4/98 REV A
Page 2
Input Specifications
Hot Swappable Modules
These shelf-mounted modules are easy and safe to install
or remove while system is operational without affecting
the overall system’s performance.
Parallel Operation and Automatic Load Sharing
Forced or passive load sharing is available between
modules of the same operating voltages in parallel
applications.
Current Limit
The Current Limit is adjustable between 0A to 50A. Upon
exceeding this limit, the rectifier automatically reduces
output voltage.
Safety
UL/CUL Recognized: UL 1950/CSA 950.
File Number: E181908
GENERAL FEATURES
Parameter
Conditions
Min
Typ
Max
Units
Operating Range
45 - 65 Hz, single phase, no taps required
176
264
VAC
Current
Adjustable
0
50
A
Efficiency
>90
%
Power Factor Correction (PFC)
>.99
MEASUREMENTS OF RM4850
Module
Weight
25 lbs.
Height
7U (12.25”)
Depth
15.25”
Width
5”
Shelf*
Weight
18 lbs.
Height
7U (12.25”)
Depth
15.25” maximum
Width
23” rack mount
* These measurements are specifically for the 200A Power Shelf for up to 4 quantity RM4850
Please contact the factory for other shelf and power plant options.
Alarm Outputs
Rectifier Fail Alarm
(RFA)
Equalize Occurring
(EQO)
High Voltage Occurring
(HVO)
Temporary Restraint Occurring
(TRO)
Thermal Shutdown Occurring
(THSD)
Open Sense Lead Has Occurred
(OS)
Low Current Alarm
(LCA)
AC Power Has Failed Alarm
(ACF)
Rectifier Fan Has Failed Alarm
(FF)
DC Breaker Is Open Alarm
(DCBKR)
AC Breaker Is Open Alarm
(ACBKR)
Note: All alarms are “Form A” relay type contacts
Control Inputs
High Voltage Shutdown
(HVSD)
Restart
(RS)
Equalize
(EQ)
Temporary Release
(TR)
Emergency Shutdown
(EMSD)
}
}
All control inputs
are initiated with
a ground closure
24VAC voltage
reference to
ground



Html Pages

1 2 3 4


데이터시트 다운로드

Go To PDF Page


링크 URL



ALLDATASHEET 가 귀하에 도움이 되셨나요?  [ DONATE ] 

Alldatasheet는?   |   광고문의   |   운영자에게 연락하기   |   개인정보취급방침   |   링크 투 데이터시트    |   링크교환   |   제조사별 검색
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com