 3 / 5 page
background image
MODEL: R5-NP1
R5-NP1 SPECIFICATIONS
ES-6107 Rev.7 Page 3/5
http://www.m-system.co.jp/
TRANSMISSION DATA DESCRIPTIONS
The DIP SW located at the side of the module switches the unit's data allocation mode.
The Data Allocation Mode 1 is used when all analog I/O modules are single-channel types. In this mode, one (1) word is
assigned for one I/O module. The second channel on the dual-channel modules cannot be used.
The Data Allocation Mode 2 is used when one or more analog I/O modules are dual-channel types. In this mode, two (2) words
are assigned for one I/O module regardless of whether the second word area is required or not. For example, discrete I/O
modules require only one (1) word, but two (2) words are automatically assigned to these modules.
■ I/O CAPACITY
In Data Allocation Mode 1, a maximum of 16 I/O modules can be mounted per node. If two-channel type analog modules are
mixed, the second channel I/O cannot be used.
In Data Allocation Mode 2, a maximum of 8 I/O modules can be mounted per node.
DATA ALLOCATION MODE 1
•Output Data
The figure below shows the allocation of the data sent
from the network module to the master.
•Input Data
The figure below shows the allocation of the data sent
from the master to the network module.
0
15
+0
Module 1
Module 2
+2
Module 3
Module 4
+4
Module 5
Module 6
+6
Module 7
Module 8
+8
Module 9
Module 10
+10 Module 11
Module 12
+12 Module 13
Module 14
+14 Module 15
Module 16
0
15
+0
Module 1
Module 2
+2
Module 3
Module 4
+4
Module 5
Module 6
+6
Module 7
Module 8
+8
Module 9
Module 10
+10 Module 11
Module 12
+12 Module 13
Module 14
+14 Module 15
Module 16
Each module takes one-word areas for input and output respectively, regardless of whether the module type is
input or output. If a module for Data Allocation Mode 2 is used, the second channel data is not transmitted.
An input module stores data in the output data area. The input data area is secured for the module but not used.



Html Pages

1 2 3 4 5


데이터시트 다운로드

Go To PDF Page


링크 URL



ALLDATASHEET 가 귀하에 도움이 되셨나요?  [ DONATE ] 

Alldatasheet는?   |   광고문의   |   운영자에게 연락하기   |   개인정보취급방침   |   링크 투 데이터시트    |   링크교환   |   제조사별 검색
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com