 4 / 5 page
background image
MODEL: R5-NP1
R5-NP1 SPECIFICATIONS
ES-6107 Rev.7 Page 4/5
http://www.m-system.co.jp/
DATA ALLOCATION MODE 2
•Output Data
The figure below shows the allocation of the data sent
from the network module to the master.
•Input Data
The figure below shows the allocation of the data sent
from the master to the network module.
0
15
+0
Module 1+0
Module 1+1
+2
Module 2+0
Module 2+1
+4
Module 3+0
Module 3+1
+6
Module 4+0
Module 4+1
+8
Module 5+0
Module 5+1
+10 Module 6+0
Module 6+1
+12 Module 7+0
Module 7+1
+14 Module 8+0
Module 8+1
0
15
+0
Module 1+0
Module 1+1
+2
Module 2+0
Module 2+1
+4
Module 3+0
Module 3+1
+6
Module 4+0
Module 4+1
+8
Module 5+0
Module 5+1
+10 Module 6+0
Module 6+1
+12 Module 7+0
Module 7+1
+14 Module 8+0
Module 8+1
Each module takes two-word areas for input and output respectively, regardless of whether the module type is
input or output. If a module for Data Allocation Mode 1 is used, all the bits for Module n+1 data turn to “0”
(unused).
An input module stores data in the output data area. The input data area is secured for the module but not used.
I/O DATA DESCRIPTIONS
The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.
■ANALOG 16 BITS DATA
0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).
With °C or Kelvin temperature unit, raw data is multiplied by 10. For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data. For example, 135.4°F is
converted into 135.
Negative values are represented in 2’s complements.
0
15
■ 16-POINT DISCRETE DATA
0
15
Input 1 (Output 1)
Input 2 (Output 2)
Input 3 (Output 3)
:
:
Input 16 (Output 16)
0 : OFF
1 : ON



Html Pages

1 2 3 4 5


데이터시트 다운로드

Go To PDF Page


링크 URL



ALLDATASHEET 가 귀하에 도움이 되셨나요?  [ DONATE ] 

Alldatasheet는?   |   광고문의   |   운영자에게 연락하기   |   개인정보취급방침   |   링크 투 데이터시트    |   링크교환   |   제조사별 검색
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com