41 / 118 page ![]() 31 T1000 Series UPS 5.6-6kVA Installation and Operation Manual – 91074-005 12.3 Battery Backup (On batteries) The following illustration shows power flow during the battery backup mode. When commercial AC power failures occur, the UPS’s batteries instantly begin supplying DC voltage to the UPS’s main inverter circuit. This circuit changes (inverts) the DC power into AC power. The AC power is available at the output of the unit. This back-up process will continue until the UPS’s battery voltage drops below a specific minimum level. When this occurs, the batteries will stop supplying power to the load. This minimum level is the rated minimum voltage (Vmin). The rated battery voltage chart on page 33 shows (Vmin). The battery backup time and discharge process is explained on page 33. 12.4 EPO (Emergency Power Off) Function These units are equipped with terminals for receiving an emergency power-off (EPO) command via a closed-contact switch at a remote location (see Terminal Block Details on Table 7-1, and terminal block location in Section 7.1). This safety feature enables quick shut-down of the UPS’s AC input breaker, output and battery circuits. Usually the emergency power off switch is installed in a central location that is easily accessible to personnel concerned with the operation of the UPS unit and the load equipment connected to it. The EPO function is initiated by pressing the switch to the closed (shutdown) position. The effect of using the EPO switch is the same whether the UPS unit is in AC input mode, battery backup mode, or the circuit bypass mode. The following figure shows the UPS condition after application of the EPO switch. NOTE: EPO operation should be limited to no more than 4 operation per minute, or 24 operations per hour. Exceeding this duty cycle will overheat the EPO components FIGURE 12-4: POWER FLOW AFTER AN EPO COMMAND FOR ALL MODELS Output Power Line Filter Inverter *Static Switch (Optional) Auto- Transformer Input Power Input Fuse Power Flow Bypass * Switches are solid state devices. MCCB Output Fuse Batteries + – Rectifier/ Chopper Negative Bus MOV Over- current Protection FIGURE 12-3: POWER FLOW IN BATTERY BACKUP FOR ALL MODELS Output Power Line Filter *Static Switch (Optional) Auto- Transformer Input Power Input Fuse Power Flow Bypass * Switches are solid state devices. MCCB Output Fuse Batteries + – Rectifier/ Chopper Inverter Negative Bus MOV Over- current Protection |
|
링크 URL |
| ALLDATASHEET 가 귀하에 도움이 되셨나요? [ DONATE ] |
Alldatasheet는? | 광고문의 | 운영자에게 연락하기 | 개인정보취급방침 | 링크 투 데이터시트 | 링크교환 | 제조사별 검색 All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |