52 / 118 page ![]() 42 T1000 Series UPS 5.6-6kVA Installation and Operation Manual – 91074-005 Remote Stop The Remote Stop is triggered by an external NO (Normally Open) dry contact switch. Power to the Remote Stop switch is about 10Vdc, and less than 20mA. When the Remote Stop switch is closed, the UPS transfers from Normal/Backup to Bypass after a 1 – 2 sec. detection delay. (See the diagram below) When the closed Remote Stop switch is opened, the UPS transfers from Bypass back to it’s initial state (Normal/Backup) after a 1 – 2 sec. detection delay. If the UPS is in bypass when the Remote Stop is closed, no action is taken. Detection Delay 1-2 Sec. Detection Delay 1-2 Sec. Remote Status Switch Normal / Backup Mode Closed Open Bypass Mode UPS Mode FIGURE 14-2: REMOTE STATUS SHUTDOWN TIMING |
|
링크 URL |
| ALLDATASHEET 가 귀하에 도움이 되셨나요? [ DONATE ] |
Alldatasheet는? | 광고문의 | 운영자에게 연락하기 | 개인정보취급방침 | 링크 투 데이터시트 | 링크교환 | 제조사별 검색 All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|