822-1002-C01 데이터시트(PDF) 18 Page - Magnetrol International, Inc.

부품명 822-1002-C01
상세설명  Kotron짰 Sentinel Models 822, 832 and 842
PDF  40 Pages
Scroll/Zoom Zoom In 100%  Zoom Out
제조업체  MAGNETROL [Magnetrol International, Inc.]
홈페이지  http://www.magnetrol.com
Logo MAGNETROL - Magnetrol International, Inc.

822-1002-C01 데이터시트(HTML) 18 Page - Magnetrol International, Inc.

Back Button 822-1002-C01 Datasheet HTML 14Page - Magnetrol International, Inc. 822-1002-C01 Datasheet HTML 15Page - Magnetrol International, Inc. 822-1002-C01 Datasheet HTML 16Page - Magnetrol International, Inc. 822-1002-C01 Datasheet HTML 17Page - Magnetrol International, Inc. 822-1002-C01 Datasheet HTML 18Page - Magnetrol International, Inc. 822-1002-C01 Datasheet HTML 19Page - Magnetrol International, Inc. 822-1002-C01 Datasheet HTML 20Page - Magnetrol International, Inc. 822-1002-C01 Datasheet HTML 21Page - Magnetrol International, Inc. 822-1002-C01 Datasheet HTML 22Page - Magnetrol International, Inc. Next Button
Zoom Inzoom in Zoom Outzoom out
 18 / 40 page
background image
DNRG
FALT
YES
NO
CAL
IGNR
ENT
ENT
ENT
ENT
ENT
STEP 7
STEP 8
STEP 7: FALT (Fault)
1. FALT (fault) refers to the choice of the alarm relay to DNRG
(de-energize) or IGNR (ignore) upon diagnosing a fault.
NOTE: The dedicated diagnostic Relay 1 will always de-energize
when a fault is detected.
When FALT is displayed, press ENT
to display DNRG.
2. If this is the desired condition, press ENT
to display
CAL.
3. If IGNR is desired, use the UP
or DOWN
arrow key to toggle between the selections.
4. When the appropriate selection is displayed, press ENT
to lock in the value and display CAL.
STEP 8: CAL (Calibration)
1. After modifying any or all of the preceding values, CAL
will lock in all the values and store them in memory.
Press ENT
to display NO (do not calibrate).
2. Press ENT
if it is desired to leave current values.
3. If new values are desired, use the UP
and DOWN
arrow keys to toggle to YES (calibrate).
4. Press ENT
to lock all the new values in memory and
return to the RUN mode.
NOTE: Ensure that the level of the process media is at the exact point
that corresponds to the choice made in Step 1 LEVL:DRY (not
covered with media) or WET (covered with media). This is crit-
ical to the proper calibration of the instrument. The unit will
take a new capacitance reading (establish a new set point)
when YES is chosen and ENT
is depressed.
ENT
ENT
ENT
ENT
ENT
ENT
ENT
50-621 Kotron Sentinel Models 822, 832 and 842 RF Point Level Switches
15



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40


데이터시트 다운로드

Go To PDF Page


링크 URL



ALLDATASHEET 가 귀하에 도움이 되셨나요?  [ DONATE ] 

Alldatasheet는?   |   광고문의   |   운영자에게 연락하기   |   개인정보취급방침   |   링크 투 데이터시트    |   링크교환   |   제조사별 검색
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com